DS-15 "FERDOM" Acid-Free Cleaning and Neutralising Agent for Central Heating Systems HVAC. Min. 10kg
1% neutralises new systems and removes oils, sludge, flux, filings, etc., 2% cleans installations whose condition prevents the use of acid. Price 1 kg.
Preparation DS-15 Ferdom - New formula
Minimum purchase quantity 10 kg, product in packages of 1 litre and 5 litres FERDOM available - HERE
Highly effective, acid-free cleaner and neutralizer for water-based central heating, refrigeration and air conditioning systems and cooling systems, etc. in industry and agriculture.
For use during normal system operation or with cleaning pumps.
For use in installations in single- and multi-family buildings and in industrial installations.
-
Penetrates, moves and dissolves rust, sludge, corrosive deposits and light mineral deposits.
-
Neutralises corrosive agents in new systems: solders, fluxes, oils, sludge, etc.
-
Ecological - acid-free with a pH close to neutral, based on the latest generation of formulations.
-
Does not require neutralisation after the cleaning process (use of a corrosion inhibitor after cleaning is recommended).
-
Dissolved deposits do not cause blockage of pumps or valves even during normal system operation.
-
Does not cause gassing of the systems and installations to be cleaned (release of gases).
-
Recommended, among others, for use with older central heating systems whose condition does not allow the use of acids.
-
For systems made of various materials, e.g. aluminium, galvanised, inox and normal plastic.
-
Application time - cleaning with a pump a few hours, during operation of the central heating system up to approx. 2 weeks.
-
The concentration of the preparation is not critical. Can be used in concentrations in the ranges close to 1% - 2%.
TECHNICAL DATA
Form: Liquid
Odour: Slightly perceptible
Colour: Light yellow
Solubility in water: In all proportions pH: 6-7.5 pH
Relative density: 1.18
Concentration: Cleaning: 1L per 50 L of water (2%), - Pre-cleaning/neutralising: 1L /100 L of water (1%).
Packaging: Ferdom; 1 litre (FD202), 5 litres (FD203) Ferpro; any quantity, minimum 10 kg (FP301)
DESCRIPTION OF APPLICATIONS
The effective acid-free agent is intended for rinsing, neutralising and cleaning water, heating installations etc;
A) New installations before commissioning to neutralise solder, fluxes, technical oils (from radiators and metal pipes) and other chemical impurities.
B) Existing water installations - to remove rust, corrosion deposits, light mineral deposits and loose substances such as sludge and contaminants that are a by-product of corrosion with minimal risk of exposing leaks.
It contains inhibitors to protect all metals and materials commonly used in heating systems. Leaving the product on for a longer period of time does not damage the installation. Cleaning can be repeated as necessary.
CLEANING METHODS
DS-15 can be used both during system operation and with a cleaning pump.
.
-Cleaning of a heating system (new or existing) during system operation consists in maintaining circulation for 7 days -14 days under normal operating conditions or for approx. 1 day maintaining a constant temperature of approx. 60-70 degrees C. The use of DS-15 does not require the boiler or radiators to be disconnected; it is advisable to use the boiler to heat the cleaning bath. When it is not possible to heat the heating installation, e.g. during the summer season, or when cleaning another installation, e.g. an air-conditioning system, the product is also effective at an ambient temperature of approx. 20°C. In this case, it is advisable to leave it in the installation longer - up to 4 weeks. In this case it is advisable to leave it in the installation longer - up to 4 weeks.
.
-Cleaning of water installations with the use of a cleaning pump. It is advisable to heat the cleaning bath to approx. 50 degrees C. Cleaning period up to approx. 6 hours. Use of Ferdom's FM1 magnetic filter (FD001) is recommended.
GENERAL RECOMMENDATIONS FOR LARGE INSTALLATIONS.
Cleaning without cleaning pump during system operation.
Recommended concentration of preparation 1% to 2% (1 to 2 litres/dm3 per 100 litres/dm3 of water) depending on the degree of contamination of the installation.
1) The preparation should be injected directly into the installation. Concentrations are not critical.
2) For optimum results - drain the installation of water and flush with tap water before cleaning.
3) Prepare the installation for cleaning. Open to full flow all valves in the system, including thermostatic controls and automatic control valves. They must be open so that no part of the circuit is disconnected during cleaning.
4) The introduction of the preparation should take place after the system has been completely / partially drained, in an open system through an expansion vessel or through a location in the system chosen by the installation team.
5) The cleaning process is faster and more effective at higher temperatures. The central heating system should include the boiler and circulation pump and operate in the normal temperature range.
6) At 60-70oC, the cleaning time can be reduced to approx. 24-48 hrs.
7)In the event that the system/boiler cannot be switched on during the
cleaning process, e.g. in summer, the DS-15 can stay in the system for approx. 4 weeks. The circulation pump should be turned on from time to time. When the installation is very dirty it is advisable to fit a Ferdom FM1 magnetic filter.
8) The cleaning process should be monitored and should last as long (and possibly be repeated) according to the results of the cleaning process monitoring.
9) The next step is to completely drain the installation and rinse it with cold water. Carefully flush the system until the water is clear. This requires the water to be changed at least three times. To protect the system for the future, the use of a corrosion inhibitor is recommended.
CLEANING OTHER WATER SYSTEMS
The cleaning method for other installations depends on their type. It is advisable to heat the cleaning bath for faster action of the product and to use a forced closed circuit. Most of the recommendations relating to central heating installations can be applied to the cleaning of other systems.
There are currently no product reviews.
Write ReviewThe owner of the online store does not guarantee that the published opinions come from consumers who have used or purchased a given product.
Wielka Brytania
Perivale
21 Wadsworth Road, 23 W.B.C.
UB6 7LQ
ferpro@ferdom.eu
Polska
Warszawa
Farbiarska 73
02-862
ferdom@britex.pl
ELIMINATOR PC407A "FERPRO" Power Flushing Pump + Set PC306 - 4 items. Mobile pump, tank. 40L, 2bar#.
Without VAT: 849.31 EUR
With VAT: 1,044.66 EURShipment:24 hours
CH-3 System Guard "FERDOM" Inhibitor 1% All Purpose Protectant. Min.Purchase 10 kg.
Without VAT:
19.98 EUR16.99 EUR
With VAT:24.57 EUR20.90 EURShipment:24 hours
FERMAG FD360 x3 Units 1" Magnetic-Separator Filter, Magnetizer 9000Gs. Hor-Vert. Conn. FERDOM
Without VAT:
153.51 EUR128.41 EUR
With VAT:188.81 EUR157.95 EURShipment:24 hours
DS-15 "FERDOM" Neutralising (1%) or Cleaning (2%) Preparation for Central Heating Systems. 5 L.
Without VAT: 110.44 EUR
With VAT: 135.84 EURShipment:24 hours
CH-1 4% "FERDOM" Inhibitor for Traditional CH Installations. 5 L. (for 125 L of water)
Without VAT: 59.07 EUR
With VAT: 72.66 EURShipment:24 hours
CH-2 System Guard 5L "FERDOM" New Generation Universal Inhibitor For CH (for 500 L of water)
Without VAT:
108.46 EUR104.51 EUR
With VAT:133.41 EUR128.55 EURShipment:24 hours






 lub czyszczac.jpg)